Technical data | IP3102-Bxxx |
---|---|
Number of inputs | 4 |
Input connections | M12, screw type |
Signal voltage | -10/0…+10 V |
Internal resistance | > 100 kΩ |
Common-mode voltage UCM | 35 V max. |
Resolution | 16 bit (for 0…10 V range: resolution 15 bit) |
Measuring error | < ±0.3="" %="" (relative="" to="" full="" scale=""> |
Conversion time | 250 ms, configurable to 5 ms |
Nominal voltage | 24 V DC (-15 %/+20 %) |
Input filter | configurable |
Sensor supply | from load supply voltage UP |
Current consumption from US (without sensor current) | see documentation |
Power supply connection | feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin |
Bit width in the process image | input: 4 x 16 bit data, optional: 4 x 8 bit control/status |
Electrical isolation | channels/control voltage: 500 V, between the channels: no, control voltage/fieldbus: depends on the bus system |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 65/66/67 (conforms to EN 60529)/variable |
Approvals | CE, UL |
8 (029) 555-8-000 | |
8 (044) 555-8-000 | |
8 (017) 255-8-000 |